Transformer Full-Load Amps and OCPD — NEC Table 450.5(B)
Free · works offline · no account · NEC 2026 tables
Enter the kVA, the phase and the two voltages. OhmBase works out the primary and secondary full-load current and reads Table 450.5(B) for the largest breaker or fuse allowed on each side, for primary-only protection or primary and secondary protection.
Open the free calculator →How the math works
Full-load current is kVA × 1,000 ÷ volts, divided again by 1.732 for three-phase. For transformers 1000 V and less, NEC Table 450.5(B) (Table 450.3(B) in the 2023 edition, same values) sets the maximum overcurrent device as a percentage of that current. Primary-only protection: 125% when the primary current is 9 A or more, 167% under 9 A, 300% under 2 A, and no secondary device is required. Primary and secondary protection: up to 250% on the primary, with 125% (9 A or more) or 167% (under 9 A) on the secondary. Only the 125% values may go up to the next standard rating (Note 1); the others are maximums, so the calculator rounds down to a standard size.
75 kVA · three-phase · 480 V primary · 208 V secondary · primary and secondary protection
- Primary FLC = 75,000 ÷ (480 × 1.732) = 90.2 A; secondary FLC = 75,000 ÷ (208 × 1.732) = 208.2 A
- Primary: 250% × 90.2 A = 225.5 A maximum → 225 A (rounds down)
- Secondary: 125% × 208.2 A = 260.2 A → next standard rating 300 A (Note 1)
FAQ
- Why can the primary breaker be 250%?
- When the secondary has its own overcurrent device at 125%, the transformer is protected from overload on the secondary side, so Table 450.5(B) lets the primary device be as large as 250% of the primary current. With primary-only protection the limit is 125%.
- When can I round up to the next breaker size?
- Only on the 125% values. Note 1 of the table allows the next higher standard rating when 125% does not land on one. The 167%, 250% and 300% values are maximums, so the device must be at or below them.
- Does this size the secondary conductors?
- No. Secondary conductors are sized separately under 240.21(C) and Table 310.16. Use the wire ampacity tool for the conductors once you know the secondary current.