Transformer Full-Load Amps and OCPD — NEC Table 450.5(B)

Free · works offline · no account · NEC 2026 tables

Enter the kVA, the phase and the two voltages. OhmBase works out the primary and secondary full-load current and reads Table 450.5(B) for the largest breaker or fuse allowed on each side, for primary-only protection or primary and secondary protection.

Open the free calculator →

How the math works

Full-load current is kVA × 1,000 ÷ volts, divided again by 1.732 for three-phase. For transformers 1000 V and less, NEC Table 450.5(B) (Table 450.3(B) in the 2023 edition, same values) sets the maximum overcurrent device as a percentage of that current. Primary-only protection: 125% when the primary current is 9 A or more, 167% under 9 A, 300% under 2 A, and no secondary device is required. Primary and secondary protection: up to 250% on the primary, with 125% (9 A or more) or 167% (under 9 A) on the secondary. Only the 125% values may go up to the next standard rating (Note 1); the others are maximums, so the calculator rounds down to a standard size.

Worked example

75 kVA · three-phase · 480 V primary · 208 V secondary · primary and secondary protection

  1. Primary FLC = 75,000 ÷ (480 × 1.732) = 90.2 A; secondary FLC = 75,000 ÷ (208 × 1.732) = 208.2 A
  2. Primary: 250% × 90.2 A = 225.5 A maximum → 225 A (rounds down)
  3. Secondary: 125% × 208.2 A = 260.2 A → next standard rating 300 A (Note 1)

FAQ

Why can the primary breaker be 250%?
When the secondary has its own overcurrent device at 125%, the transformer is protected from overload on the secondary side, so Table 450.5(B) lets the primary device be as large as 250% of the primary current. With primary-only protection the limit is 125%.
When can I round up to the next breaker size?
Only on the 125% values. Note 1 of the table allows the next higher standard rating when 125% does not land on one. The 167%, 250% and 300% values are maximums, so the device must be at or below them.
Does this size the secondary conductors?
No. Secondary conductors are sized separately under 240.21(C) and Table 310.16. Use the wire ampacity tool for the conductors once you know the secondary current.