Equipment Grounding Conductor Size — NEC Table 250.122
Free · works offline · no account · NEC 2026 tables
The ground wire is sized from the breaker, not the load. Enter the rating of the overcurrent device ahead of the circuit and OhmBase reads Table 250.122 for copper or aluminum; tell it the conductors were upsized and it applies the proportional increase the Code requires.
Open the free calculator →How the math works
NEC Table 250.122 lists the minimum equipment grounding conductor by the rating of the overcurrent device ahead of the circuit: 15 A → 14 AWG copper, 20 A → 12 AWG, 60 A → 10 AWG, 100 A → 8 AWG, 200 A → 6 AWG, and so on. When the ungrounded conductors are increased in size for any reason other than ambient or bundling adjustment, 250.122(B) requires the EGC to be increased in proportion to the increase in circular-mil area, and 250.122(A) says it never has to be larger than the circuit conductors.
20 A breaker · copper · 12 AWG required but 6 AWG installed for voltage drop
- Table 250.122, 20 A row → 12 AWG copper
- Upsize ratio = 26,240 ÷ 6,530 circular mils = 4.02
- 6,530 × 4.02 = 26,240 cmil → 6 AWG copper EGC
FAQ
- Why is the ground wire sized from the breaker?
- The EGC only carries current during a fault, and the breaker rating sets how much current can flow before it clears. Table 250.122 is organized by that rating.
- What if I upsized for voltage drop?
- The EGC must grow by the same ratio of circular-mil area as the ungrounded conductors (250.122(B)). The calculator does that math and rounds up to a standard size.
- Does this cover ratings up to 6,000 A?
- Yes. Every row of Table 250.122, 15 A through 6,000 A, copper and aluminum. The 2023 and 2026 tables are the same.